Ct2a] [ct2b] [db`a] [db`b, Operation-pid a or b, Cycle time, output 2 – Watlow Series 988 User Manual
Page 92: Dead band a or b
5.16
WATLOW Series 988 User’s Manual
Operation Menus, Chapter 5
Operation-PID A or B
Cycle Time, Output 2
Select the time, in seconds, of a complete on/off cycle.
[Ct2A] This prompt appears only if [CntL] (Global Menu) is not set to
[CSCd] and [Pb2A] is set higher than [```0].
If
Default
↓
↓
mechanical
[``%0] … [`1)0] … [99(9]
relay
[Ct2A]
[Ct2A]
[Ct2A]
outputs
open collector
[brSt]
[``)1] … [``!0] … [99(9]
or solid-state
[Ct2A]
[Ct2A]
[Ct2A]
[Ct2A]
relay outputs
Dead Band A or B
Select the width of the zone between the action of the heating output
and the cooling output. If you select a positive value the heat and cool
outputs cannot be energized at the same time. If you select a negative
value, both outputs can be energized at the same time.
• If a process input is selected the decimal precision will be determined by
the
[`dEC1] setting (Input Menu).
[db`A] This prompt appears only if [Pb2A] is set higher than [```0] and
one output performs heating action and the other performs cooling action.
If
Default
↓
↓
[``°F]
[-999] … [```0] … [`999]
[`C_F]
[db`A]
[db`A]
[db`A]
(Global Menu)
[``°C]
[-555] … [```0] … [`555]
[`C_F]
[db`A]
[db`A]
[db`A]
(Global Menu)
a process
[-999] … [```0] … [`999]
units
input is selected
[db`A]
[db`A]
[db`A]
[Ct2A]
[Ct2b]
[db`A]
[db`b]
˜
NOTE:
The PID B Menu
appears only on
controllers with
enhanced software
(98_B-_ _ _ _-_ _ _ _).