4.39

Setup Menus, Chapter 4

Setup-Global

Crossover Process Value

Select the process value at which the control algorithm will crossover
between PID A and PID B.
PID A is active below this value and PID B is
active above this value.

• This value cannot be set lower than range low 1

[`rL1] or higher than

range high 1

[`rH1].

[Proc] This prompt appears only on controllers with [Pid2] set to [Proc].

Default

[`rL1]

[`rH1]

[Proc]

[Proc]

Crossover Set Point Value

Select the set point value at which the control algorithm will
crossover between PID A and PID B.
PID A is active below this value and
PID B is active above this value.

• This value cannot be set lower than range low 1

[`rL1] or higher than

range high 1

[`rH1].

[StPt] This prompt appears only on controllers with [Pid2] set to [StPt].

Default

[`rL1]

[`rH1]

[StPt]

[StPt]

[Proc]

[StPt]