4.9

Setup Menus, Chapter 4

Setup-Input

˜

NOTE:
If

[``no] is selected

for

[`In2] none of

the other input 2
prompts will
appear.

Input 2

Select sensor type for input 2. This selection must match the sensor
type connected to terminals 18, 19 and 20. See Appendix for more infor-
mation about sensors.

• Changing the value of

[`In2] changes all other prompts to the facto-

ry default values, except the Communications and Lockout menus,
the

[`C_F] prompt in the Global Menu and the [`dFL] prompt in the

Calibration Menu. If you change the value, the default warning
[dFLt] will flash in the upper display.

• Changes do not take effect automatically after five seconds; you must

press the Mode key µ to enter the sensor type change and advance to
the next prompt.

[`In2] This prompt and other Input 2 prompts appear only on controllers
equipped with input 2 hardware (not 98_ _-_0_ _-_ _ _ _).

[`In2]

Input 2 continued
on next page.

[`In2]

If

Default

↓ ↓

98_ _-1_ _ _-_ _ _ _

no DIP

J

K

T

N

E

W5

W3

Pt2

0-50mV

[``no]

[```J]

[```H]

[```t]

[```n]

[```E]

[```C]

[```d]

[`Pt2]

[0-50]

thermocouple

[``In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

only

98_ _-2_ _ _-_ _ _ _

Input 2 DIP

J

K

T

N

E

W5

W3

Pt2

0-50mV

[``no]

[```J]

[```H]

[```t]

[```n]

[```E]

[```C]

[```d]

[`Pt2]

[0-50]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

thermocouple

Input 2 DIP

R

S

B

[``no]

[```r]

[```S]

[```b]

[`In2]

[`In2]

[`In2]

[`In2]

thermocouple

Input 2 DIP

RTD

RTD (0.1°)

[``no]

[`rtd]

[`r†d]

[`In2]

[`In2]

[`In2]

RTD

Input 2 DIP

4-20mA

0-20mA

0-5VÎ

1-5VÎ

0-10VÎ (dc)

[``no]

[4-20]

[0-20]

[`0-5]

[`1-5]

[0-10]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

[`In2]

process

O
N

1

2

3

O
N

1

2

3

O
N

1

2

3

O
N

1

2

3

CAUTION:
Changing the value
of

[`In2] changes

most other prompts
to the factory
default values.
Document all set-
tings before chang-
ing sensor type.
Verify the correct
sensor type before
making a change.
Failure to follow
this guideline could
result in damage to
equipment or prop-
erty. Document all
settings before
changing sensor
type.