WATLOW Series 988 User’s Manual

8.17

General Software Features, Chapter 8

General Software

Sample Application
An engineer needs to control the temperature of a muffle furnace. The fur-
nace set point must be ramped up at a defined rate to prevent stressing
the muffle and other system components. By enabling the ramp to set
point function in the Series 988, the engineer can control the rate at
which the set point will rise. Ramp to set point is enabled in the Global
Menu using the Ramping Function prompt

[``rp]. To ramp on start up

only, select start

[Strt]. To ramp on start up and on any set point

changes, select set point

[StPt]. The ramp rate [rate] is in degrees per

minute.

For further protection of the system, output 2, 3 or 4 can be configured as
a rate alarm, monitoring the rate of increase or decrease in the process
variable on input 1. The Alarm Low

[A2LO] and Alarm High [A2HI]

prompts (The “2” in these examples refers to output 2.) establish the
ramp-down and ramp-up rate set points, respectively, in degrees per
minute.

TL

W

WA

PROCESS

L1

L2

L3

L4

DEV

% OUT

DISPLAY

MODE

AUTO

MAN

SERIES 988

input 1

output 1

limit

limit
sensor

temperature
sensor

heaters

heaters

Muf f le Furna c e

Figure 8.17 -
Muffle furnace with
ramp to set point.