beautypg.com

Output 4 wiring, 15 output 4 wiring, Switched dc, open collector – Watlow Series 988 User Manual

Page 25: Ac outputs, External signal conditioner power supply, Controllers with output 4 (r, s, or u)

background image

WATLOW Series 988 User’s Manual

2.15

Installation and Wiring, Chapter 2

Figure 15b —

Switched DC, Open Collector

98 _ _ - _ _ _ _ - _ C _ _

Maximum voltage: 42VО

О (dc)

Maximum current: 1A

Figure 15a —

AC Outputs

Solid-state Relay with Contact Suppression

98 _ _ - _ _ _ _ - _ B _ _

0.5 amps, minimum off-state impedance: 20K

Electromechanical Relay with Contact Suppression
(Suppression between NO and COM contacts only)

98 _ _ - _ _ _ _ - _ D _ _ _

Form C, 5 amps, minimum off-state impedance: 20K

Electromechanical Relay without Contact Suppression

98 _ _ - _ _ _ _ - _ E _ _ _

Form C, 5 amps, off-state impedance: 31M

Solid-state Relay without Contact Suppression

98 _ _ - _ _ _ _ - _ K _ _ _

0.5 amps, off-state impedance: 31M

Output 4 Wiring

External

Load

COM

L1

L2

Fuse

NO

5

6

NC

(#7 for D & E outputs only)

7

5

External

Load

6

+

7

-

COM

Figure 15c —

External Signal Conditioner Power Supply

98 _ _ - _ _ _ _ - _ T _ _

5

6

+

-

+V

-V

Transmitter

4-20mA out

Input
1 or 2

+

-

Controllers with Output 4 (R, S, or U)

For data communications wiring refer to “Data Communications
with the Watlow Series 988 Family of Controllers”
manual. This
manual can be downloaded from Watlow’s website at www.wat-
low.com,
Product Technical Information - Controls.

NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a signal con-
ditioner connected
to input 1 or input 2.

˜

NOTE:
See Chapter 1 for
power supply DIP
switch information.

NOTE:
Successful installa-
tion requires five
steps:
• Model number and
software choice
(Appendix);
• DIP switch set-
tings (Chapter 1);
• Sensor match
(Chapter 2 and
Appendix);
• Sensor installation
(Chapter 2); and
• Wiring (Chapter 2).

+

Internal Circuitry

5

6

7

790

19 to 32VÎ (dc)

NOTE:
Switching inductive
loads (relay coils,
solenoids, etc.) with
the mechanical
relay or solid state
relay output options
requires using an
R.C. suppressor.
Watlow carries the
R.C. suppressor
Quencharc brand
name, which is a
trademark of ITW
Paktron. Watlow
Part No. 0804-0147-
0000.

Loop powered