Setup-input, Rl2] [`rh2 – Watlow Series 988 User Manual

Page 40

background image

4.12

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

Setup-Input

Default

Default

Default

Default

[``°F]

[``°C]

[`rL2]

[`rH2]

[`rL2]

[`rH2]

[```J]

[``32]…[1500]

[```0]…[`816]

98_ _-1_ _-_ _ _ or

[`in2]

[`rL2]

[`rH2]

[`rL2]

[`rH2]

98_ _-2_ _-_ _ _

(K)

[```H]

[-328]…[2500]

[-200]…[1371]

[```t]

[-328]…[`750]

[-200]…[`399]

[```n]

[``32]…[2372]

[```0]…[1300]

[```E]

[-328]…[1470]

[-200]…[`799]

(W5)

[```C]

[``32]…[4200]

[```0]…[2316]

(W3)

[```d]

[``32]…[4200]

[```0]…[2316]

[`Pt2]

[``32]…[2543]

[```0]…[1395]

high impedance

[0-50]

[-999]…[`999]

[-573]…[`573]

[```r]

[``32]…[3200]

[```0]…[1760]

98_ _-2_ _-_ _ _ only

[```S]

[``32]…[3200]

[```0]…[1760]

[```b]

[``32]…[3300]

[```0]…[1816]

[`rtd]

[-328]…[1472]

[-200]…[`800]

[`r†d]

[-9(9]…[99(9]

[-7#3]…[53&7]

[4-20]

[-999]…[9999]

units

[0-20]

[-999]…[9999]

units

[`0-5]

[-999]…[9999]

units

[`1-5]

[-999]…[9999]

units

[0-10]

[-999]…[9999]

units

[0-50]

[-999]…[9999]

units

[0=00]

[-999]…[9999]

units

slidewire

[SLid]

[`100]…[1200]

ohms

current

[Curr]

[```0]…[``50]

amps

potentiometer

[`POt]

[```0]…[1200]

ohms

˜

NOTE:
These values do not
affect the low or the
high set point limit
for process alarms.

[`rL2]
[`rH2]

Range Low 2 and
Range High 2 con-
tinued from previ-
ous page.

˜

NOTE:
When high imped-
ance

[0-50] is

selected for input 1
the range high for
both

[``°C] and

[``°F] can be
extended to

[9999]

.

The range low when
[``°C] is selected
can be extended to

[-999]

.