4.24

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

Setup-Output

Latching 2

Select whether alarm 2 will be latching or non-latching. A latching
alarm

[`LAt] must be turned off manually. A non-latching alarm [`nLA]

turns off when an alarm condition no longer exists.

[LAt2] This prompt appears only on controllers equipped with output 2
hardware and with

[`Ot2] set to [`AL2] or [AL2n].

Default

[`nLA]

[`LAt]

[LAt2]

[LAt2]

Silencing 2

Select silencing to inhibit alarm 2 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between

[A2LO] and

[A2HI].

[`AL2] This prompt appears only on controllers equipped with output 2
hardware and with

[`Ot2] set to [`AL2] or [AL2n].

Default

[`OFF]

[``On]

[SIL2]

[SIL2]

˜

NOTE:
See Chapter 7 for
more information
on alarms.

[LAt2]

[SIL2]