WATLOW Series 988 User’s Manual

4.27

Setup Menus, Chapter 4

Setup-Output

Latching 3

Select whether alarm 3 will be latching or non-latching. A latching
alarm

[`LAt] must be turned off manually. A non-latching alarm [`nLA]

turns off when an alarm condition no longer exists.

[LAt3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98_ _-_ _ _ _-B_ _ _, 98_ _-_ _ _ _-J_ _ _ or
98_ _-_ _ _ _-K_ _ _) or switched dc (98_ _-_ _ _ _-C_ _ _) and with

[`Ot3] set

to

[`AL3] or [AL3n].

Default

[`nLA]

[`LAt]

[LAt3]

[LAt3]

Silencing 3

Select silencing to inhibit alarm 3 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between

[A3LO] and

[A3HI].

[SIL3] This prompt appears only on controllers equipped with output 3
hardware for a relay (98_ _-_ _ _ _-B_ _ _, 98_ _-_ _ _ _-J_ _ _ or
98_ _-_ _ _ _-K_ _ _) or switched dc (98_ _-_ _ _ _-C_ _ _) and with

[`Ot3] set

to

[`AL3] or [AL3n].

Default

[`OFF]

[``On]

[SIL3]

[SIL3]

˜

NOTE:
See Chapter 7 for
more information
on alarms.

[LAt3]

˜

NOTE:
See Chapter 7 for
more information
on alarms.

[SIL3]