beautypg.com

Dec1, Setup-input, Decimal 1 – Watlow Series 988 User Manual

Page 32

background image

4.4

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

[`In1]

Input 1 continued
from previous
page.

Setup-Input

If

Default

Input 1 DIP

RTD

RTD(0.1°)

[`rtd]

[`r†d]

[`In1]

[`In1]

RTD

Input 1 DIP

4-20mA

0-20mA

0-5VÎ

1-5VÎ

0-10VÎ (dc)

[4-20]

[0-20]

[`0-5]

[`1-5]

[0-10]

[`In1]

[`In1]

[`In1]

[`In1]

[`In1]

process

Decimal 1

Select the decimal point location for process type input 1 data. This
prompt, in conjunction with the Range Low and Range High prompts,
allows you to format and limit units of measure for process 1.

• All prompts with units of measure related to input 1 will display in the

selected decimal format.

• This affects propbands, alarm set points, process set points, calibration

offsets, deadbands and ranges.

[dEC1] This prompt appears only if you have set input 1 [`In1] to a
process input or to a thermocouple input set to 0-50mV.

Default

[```)]

[``)0]

[`)00]

[)000]

[dEC1]

[DEC1]

[dEC1]

[dEC1]

O
N

1

2

3

O
N

1

2

3

[dEC1]