beautypg.com

General software, 50% output, 10% output – Watlow Series 988 User Manual

Page 119: 100% output, 66% output, 1 on, 1 off, 1 on, 9 off, 10 on, 0 off

background image

WATLOW Series 988 User’s Manual

8.3

General Software Features, Chapter 8

General Software

TL

W

WA

PROCESS

L1

L2

L3

L4

DEV

% OUT

DISPLAY

MODE

AUTO

MAN

SERIES 988

input 1

output 1

QPAC

with

QCD

input

limit

S e mic onduc t or O v e n

temperature
sensor

limit
sensor

heated platen

50% output

1 on, 1 off

10% output

1 on, 9 off

100% output

10 on, 0 off

66% output

2 on, 1 off

Sample Application
A Series 988 controls a heated platen in a semiconductor oven. Previously
it used a power control requiring a 4-20mA signal to implement burst-fire
control. We have replaced the power control with a Watlow Loyola QPAC
with a QCD card that accepts a signal directly from an open-collector out-
put of the Series 988. This gives smooth control at a lower overall system
cost.

Figure 8.3b -
Semiconductor
oven with burst fire.

Figure 8.3a - Sine
waves of burst fire
settings.