4.40

WATLOW Series 988 User’s Manual

Setup Menus, Chapter 4

Setup-Global

Event Input 1

Select the effect of closing the event input 1 switch.

[``no] disables event input 1.

[`LOC] locks out the front panel keys.

[`ALr] resets an alarm.

[A-M] switches the controller to manual mode at the power level set at

[FAIL] (Global Menu) and disables the Auto/Man åkey.

[`OFF] turns all control outputs off (de-energize relays).

[`Pid] switches from PID A to PID B.

[Actn] selects the opposite control action for output 1 and 2.

[`rSP] switches to a remote set point.

[IdSP] switches to an idle or second set point.

[`Ei1] This prompt always appears.

Default

[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [`rsp] [IdSP]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

[`Ei1]

Event Input 2

Select the effect of closing the event input 2 switch. The selections are
the same as for event input 1.

[`Ei2] This prompt appears only on controllers equipped with hardware
for a second event input (98_ _-_5_ _-_ _ _ _) and with

[`In2] set to

[`Ei2].

Default

[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [IdSP]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei2]

[`Ei1]

[`Ei2]