Ei1] [`ei2, Setup-global, Event input 1 – Watlow Series 988 User Manual
Page 68: Event input 2

4.40
WATLOW Series 988 User’s Manual
Setup Menus, Chapter 4
Setup-Global
Event Input 1
Select the effect of closing the event input 1 switch.
•
[``no] disables event input 1.
•
[`LOC] locks out the front panel keys.
•
[`ALr] resets an alarm.
•
[A-M] switches the controller to manual mode at the power level set at
[FAIL] (Global Menu) and disables the Auto/Man åkey.
•
[`OFF] turns all control outputs off (de-energize relays).
•
[`Pid] switches from PID A to PID B.
•
[Actn] selects the opposite control action for output 1 and 2.
•
[`rSP] switches to a remote set point.
•
[IdSP] switches to an idle or second set point.
[`Ei1] This prompt always appears.
Default
↓
[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [`rsp] [IdSP]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
[`Ei1]
Event Input 2
Select the effect of closing the event input 2 switch. The selections are
the same as for event input 1.
[`Ei2] This prompt appears only on controllers equipped with hardware
for a second event input (98_ _-_5_ _-_ _ _ _) and with
[`In2] set to
[`Ei2].
Default
↓
[``no] [`LOC] [`ALr] [A-M] [`OFF] [`Pid] [Actn] [IdSP]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei2]
[`Ei1]
[`Ei2]