beautypg.com

Setup steps, Indicator lights, Over view – Watlow MICRODIN User Manual

Page 9

background image

Over

view

Setup Steps

1. Set up communications.

2. Set the controller’s address and baud speed with the DIP switches on the top

panel (see

Chapter 2

, Communications Setup). The controller uses eight data

bits with no parity.

3. Mount the controller (see

Chapter 3

, Wiring).

4. Wire the controller (see

Chapter 3

, Wiring).

5. Communicate with MicroDIN via an EIA-485 network with Modbus

RTU protocol.

Communications
Green Light pulsates when the
controller sends or receives
valid data over its network port.
• If it does not light up, check
the controller address and the
communications setup.

Input Error
Red Light is lit if there is a
sensor problem. If it is lit:
• Verify the sensor wiring,
polarity and function.
• Rewire or replace as
necessary.

Address Field
Record the unit’s address in
erasable marker here.

Address

Power

Comms

Alarm

Temperature Controller

MicroDIN

Temperature Controller

MicroDIN

Control
Output

Input
Error

Figure 1.3 - MicroDIN
indicator lights

Indicator Lights

Power
Green light stays
lit when the power is on
and the controller is ok.
• If it isn’t on or pulsates,
check your power source.

Control Output
Green light is lit or flashes
when the control output is
energized.
• If it does not light up, the
output is not turning on.

Alarm
Red Light is lit during an
input alarm condition.
If it is lit:
• Correct alarm condition
or change alarm
configuration.
• Reset the alarm if it is
latched.

Wa t l o w M i c r o D I N 1 . 3