Alarm Output Group continued
Alarm Output Group – Setup
Alarm Low
• Set the low alarm set point.
• Read/write
• Modbus: 321
Range
process: sensor range low to Alarm High (Alarm Output Group)
deviation: -1999 to -1
Default
process: sensor range low
deviation: -1999
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Affected by
Sensor Type (Input Group) determines range of setting and
default.
Input Type (Input Group) determines range of setting and
default.
Alarm Type (Alarm Output Group) determines range of setting
and default.
C or F (System Group) converts and determines range of setting.
Alarm High
• Set the high alarm set point
• Read/write
• Modbus: 322
Range
process: Alarm Low (Alarm Output Group) to sensor range high
deviation: 1 to 9999
Default
process: sensor range high
deviation: 9999
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Affected by
Sensor Type (Input Group)
determines range of setting and default
Input Type (Input Group)
determines range of setting and default
Alarm Type (Alarm Output Group)
determines range of setting and default
C or F (System Group)
converts and determines range of setting