Calibration group, Parameters, Enter calibration mode – Watlow MICRODIN User Manual

Page 78: Calibration commands

background image

5 . 3 0 Wa t l o w M i c r o D I N

= R e a d O n l y ;

= R e a d / W r i t e ;

= Tu r n O n / O f f

ON

Parameters

Calibration Group continued

Enter Calibration Mode

• Enter calibration mode, to calibrate the controller.
• Must be in diagnostics mode to enter calibration mode
• Read/write
• Modbus: 1600

Range

0 to 1414 and 1416 to 9999: exit calibration mode
1415: enter calibration mode

Default

0

Active

if the controller is in diagnostics mode

Calibration Commands

• Measure and store a selected input calibration value.
• Write
• Modbus: 1603

Range

0: no calibration
1: store 0.000mV input
2: store 50.000mV input
3: store CJC input (32°F Type J, compensated)
4: store ground input (S1, S2 and S3 shorted)
5: store RTD lead resistance (S1 and S2 shorted)
6: store 15.00 ohms
7: store 380.00 ohms
10: store 4mA input

Default

0

Active

if the controller is in calibration mode.

ç

CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

See Disable Non-
volatile Memory
(System Group).

Calibration Group

Enter Calibration Mode ............................

5.30

Calibration Commands .............................

5.30

Restore Factory Calibration ....................

5.30

Reset Factory Defaults...............................

5.31

NOTE:

See page
6.6

for the

calibration
procedures.