Parameters, Alarm latching mode, Alarm silencing mode – Watlow MICRODIN User Manual
Page 69: Alarm logic, Alarm output group continued
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 2 1
ON
Range
0: both
1: high side only
2: low side only
Default
0: both
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Alarm Latching Mode
• Turn alarm latching on or off. When latching is active, the alarm
will remain on after the alarm condition ends. It must be turned
off manually.
• Read/write
• Modbus: 721
Range
0: no
1: yes
Default
0: no
Active
if Set Alarm Output Function (Alarm Output Group) is set to
alarm
Alarm Silencing Mode
• Turn alarm silencing on or off. When silencing is active and the
controller is first turned on, the alarm cannot become active until
the process temperature leaves the alarm range. Also, alarms can
be manually silenced after one occurs. Entering the normal
operation range resets the silence.
• Read/write
• Modbus: 722
Range
0: no
1: yes
Default
0: no
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Alarm Logic
• Select alarm output logic.
• Read/write
• Modbus: 724
Range
0: alarm condition de-energizes output (open)
1: alarm condition energizes output (closed)
Default
0
Active
if Alarm Output Function (Alarm Output Group) is set to alarm
Alarm Output Group continued