Control Output Group continued
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 1 1
ON
Operation Group
Monitor
Operation Mode .........................................
Use
Operation Mode .........................................
User Set Point ...........................................
Manual Output Power ..............................
Operation Group – Monitor
Operation Mode
• Monitor the operation mode. Normally follows the user selected
mode. It returns to the previous state after an error clears.
• Read only
• Modbus: 200
Range
0: off
1: auto
2: manual control (user selected)
3: manual control (due to error)
Default
auto
Active
always
Operation Group – Use
User Operation Mode
• Select whether the controller is under auto or manual control.
• Read/write
• Modbus: 301
Range
0: auto
1: manual
Default
0: auto
Active
always
Affects
Manual Output Power (Operation Group) manual or manual due
to error