Alarm output group, Alarm output group – monitor, Parameters – Watlow MICRODIN User Manual
Page 65: Alarm condition
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 1 7
ON
Alarm Output Group – Monitor
Alarm Condition
• Monitor the alarm state.
• Read only
• Modbus: 106
Range
0: no alarm
1: high alarm
2: low alarm
3: high latched alarm
4: low latched alarm
5: high silenced alarm
6: low silenced alarm
7: high latched silenced alarm
8: low latched silenced alarm
9: waiting for in range alarm
10: disabled alarm
11 error alarm
Default
none
Active
always
PID Group continued
Alarm Output Group
Monitor
Alarm Condition ........................................
Alarm Output Hardware ..........................
Use
Clear Alarm ...............................................
Silence Alarm ............................................
Setup
Alarm Low .................................................
Alarm High ................................................
Alarm Output Function ............................
Alarm Type ................................................
Alarm Hysteresis .......................................
Alarm Active Sides ....................................
Alarm Latching Mode ...............................
Alarm Silencing Mode ...............................
Alarm Logic ...............................................
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
volatile Memory
(System Group).