Error group, Error group – monitor, Parameters – Watlow MICRODIN User Manual
Page 70: Open loop error, Open loop detect

Parameters
Error Group continued
Error Group
Monitor
Open Loop Error ........................................
Open Loop Detect ......................................
Input Error ................................................
System Error .............................................
Use
Clear Error ................................................
Setup
Input Error Action .....................................
Error Clearing Mode .................................
ç
CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.
See Disable Non-
volatile Memory
(System Group).
5 . 2 2 Wa t l o w M i c r o D I N
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
ON
Error Group – Monitor
Open Loop Error
• Read the open loop error status. An open loop indicates that the
output is not responding appropriately to the input.
• Read only
• Modbus: 210
Range
0: no error
1: open loop error detected
Default
none
Active
always
Open Loop Detect
• Turn the open loop detect feature on or off.
• Read/write
• Modbus: 904
Range
0: off
1: on
Default
0: off
Active
always
Affects
Read Open Loop Error (Error Group) must be on to activate
Read Open Loop Error
ON