Parameters, Derivative term, Enter diagnostics mode (set) – Watlow MICRODIN User Manual
Page 77: Test displays, Test outputs, Diagnostics group continued
![background image](/manuals/359130/77/background.png)
Parameters
= R e a d O n l y ;
= R e a d / W r i t e ;
= Tu r n O n / O f f
Wa t l o w M i c r o D I N 5 . 2 9
ON
Derivative Term
• Monitor the derivative term. See
PID control.
• Read only
• Modbus: 207
Range
-100.0 to 100.0
Default
none
Active
always
Enter Diagnostics Mode (Set)
• Enter the diagnostics mode to test indicator lights and outputs and
to enter the calibration mode.
• Read/write
• Modbus: 1512
Range
0 to 1788 and 1790 to 9999: exit the diagnostics mode
1789: enter the diagnostics mode
Default
0
Active
always
Test Displays
• Test the indicator lights on the front panel.
• Read/write
• Modbus: 1513
Range
0: turn off all indicator lights
1: turn on the cyclic display test
Default
0
Active
if the controller is in the diagnostics mode
Test Outputs
• Test both outputs.
• Read/write
• Modbus: 1514
Range
0: turn both outputs off
1: turn the control output on and the alarm output off
2: turn the control output off and the alarm output on
Default
0
Active
if the controller is in diagnostics mode
Diagnostics Group continued