Purpose
To meet Mark CE requirements, this addendum provides supplemental information to the
MicroDIN User’s Manual (W0UD-XUMN Rev A), and the
MicroDIN Quick Start Guide (W0UD-XQRN Rev A).
Power Supply Rating
MicroDIN CE Mark compliance requires an IEC 742 rated power supply. This applies to
the following power supply references:
User’s Manual: p. 3.2, 3.7 (fig. 3.7e), 3.10 (fig. 3.10), 3.11 (fig. 3.11) and A.14
Quick Start Guide: p. 13 (fig. 3.4e), 16, 17 and 22
External DC Output Fusing
Also, a customer supplied 1A fuse is required for external dc output connection to meet CE
compliance. This applies to the following external dc output references:
User’s Manual: p. 3.7 (fig. 3.7b)
Quick Start Guide: p. 13 (fig. 13b)
External DC Output Derating
For MicroDIN CE Mark compliance, external load switching (maximum) for an open
collector is derated from 60V @ 1A to 42V @ 1A. This applies to the following output rating
references:
User’s Manual: p. 3.7 (fig. 3.7b) and A.14
Quick Start Guide: p. 13 (fig. 13b) and 22
(1044)
W 0 U D - X A D N R e v A
Wa t l o w M i c r o D I N C E A d d e n d u m 1
A p r i l 1 9 9 7
CE Addendum
Addendum
MicroDIN User’s Manual & Quick Start Guide
A
Figures 3.7b
and 13b—
Control Output,
Open Collector
with External
Power Supply
Figure 3.7e—
Power Wiring
10
1 2 3 4 5 6 7 8 9
24V
‡
(ac/dc)
- +
1 2 3 4 5 6 7 8 9 10
+
External
Load
dc+
COM
dc-
+
-
Power
Supply
60V max.
1A max.
Fuse
-
-
-
NOTE: An IEC
742 rated power
supply is
required for CE
compliance.
CE Compliance