Input Group – Monitor

Input Actual

• Monitor the input value.
• During an input error state, this will read 9999 if Read Control

Output (Control Output Group) is set to heat or -1999 if it is set to
cool.

• Read only
• Modbus: 100

Range

input type range

Default

none

Active

always

Input Error

• Monitor the input error status.
• Read only
• Modbus: 101

Range

0: no error
1: analog-to-digital signal under range
2: sensor under range
3: sensor over range
4: analog-to-digital over range

Default

none

Active

always

ç

CAUTION:
Avoid writing
continuously to
EEPROM memory.
Continuous writes
may result in
premature control
failure, system
downtime and
damage to
processes and
equipment.

See Disable Non-
volatile Memory
(System Group).

Input Group

Monitor
Input Actual ...............................................

5.4

Input Error ................................................

5.4

Setup
Sensor Type ...............................................

5.5

Input Type .................................................

5.5

Range Low .................................................

5.6

Range High ................................................

5.6

Calibration Offset ......................................

5.6

Filter Time Constant ................................

5.7

Input Error Action .....................................

5.7