4.7.16 EDIT TRIGGER LATCH STATUS
|--------------|
Display: ¦ a SEG TR DI¦
¦ TRIG? UNLATCH¦
|--------------|
The ? flashes.
YES Change latch state of this trigger.
Lower display UNLATCH
UP/DOWN Select unlatch or latch status.
ENTER Assign latch status for this trigger. Display advances to Edit
Trigger Input Number for the next trigger.
BACK Return to Edit Segment Triggers.
NO Leave latch state assignment for this trigger as it is. Display
advances to Edit Trigger Input Number for next trigger.
BACK Return to Edit Segment Triggers.
4.7.17 EDIT SEGMENT TOLERANCE
Use this menu to edit the tolerance value assigned to this segment. The tolerance is a value from -
99 to 99, or OFF, that specifies a process variable limit for assured soak. If a positive value is
entered the process variable is assured to be no higher than setpoint + the tolerance value. If a
negative value is entered the process variable is assured to be no lower than setpoint - tolerance. If
OFF is specified no tolerance checking is done.
Whenever a loop is out of tolerance the status display will show a 'T' and the segment clock will
stop running. When the loop returns to within tolerance the segment clock will resume. If the
cumulative time out of tolerance for the entire segment exceeds the maximum out-of-tolerance
time specified for this profile, a tolerance alarm is generated.
|----------------|
Display: ¦ x SEGMENTyy ¦
¦ SEG TOLRANCE?zz¦
|----------------|
The ? flashes.
x is the profile designator [A-L].
yy is the segment number [1-20].
zz is the tolerance value for assured soak.