7 setup ramp/soak profile, 1 select a profile for editing, 7 setup ramp/soak profile -45 – Watlow 12LS Controller User Manual
Page 78: 1 select a profile for editing -45
4-45
|-----------------------------------------------------|
¦ NOTE: For RAMP AND SOAK option, if the loop is run- ¦
¦ ning a ramp and soak profile, forcing it into manual¦
¦ removesthe loop from ramp and soak mode. The user ¦
¦ must reassign and restart the profile to return to ¦
¦ automatic ramp and soak operation. ¦
|-----------------------------------------------------|
4.7 SETUP RAMP/SOAK PROFILE
Press YES at this prompt to setup or edit stored ramp and soak profile data including :
- profile number
- copy one profile to another
- maximum out-of-tolerance time
- ready state setpoint
- ready event (digital output) states
- segment number
- segment time
- segment setpoint
- segment events
- segment triggers
- segment tolerance
- last segment
|-----------------------------------------------------|
¦ NOTE: When leaving ramp and soak mode the loop is ¦
¦ placed in MANUAL mode and the output is set to 0. ¦
|-----------------------------------------------------|
NOTE: This prompt will appear only if the 12LS has the ramp and soak option
installed.
4.7.1 SELECT A PROFILE FOR EDITING
This menu allows selection of one of twelve profiles [A-L] for editing. The default profile number
displayed in the prompt is either the last profile edited or PROFILE A if none has been edited.
|-----------------|
Display: ¦ EDIT RAMP & SOAK¦
¦ PROFILE ? x ¦
|-----------------|
The ? flashes.
x is the profile designator [A-L].
YES Select a profile other than the default profile displayed.
Lower display PROF = x