beautypg.com

Watlow 12LS Controller User Manual

Page 105

background image

8-4

The following examples show the output code for specific output types:

Output Configuration Hex Code
--------------------------------------- --------
DZC Digital Output, Automatic control 00
Time Proportioned Digital Output, Automatic control 01
Analog output, Automatic control 02
DZC Digital Output, Manual Control 04
Time Proportioned Digital Output, Manual control 05
Analog output, Manual control 06
ON/OFF Digital Output, Automatic control 40
ON/OFF Digital Output, Manual control 44
DZC Output, Automatic Control, Inverted Output 80
Time Proportioned Output, Automatic Control, Inverted Output 81
Analog Output, Automatic Control, Inverted Output 82
DZC Output, Manual Control, Inverted Output 84
Time Proportioned Output, Manual Control, Inverted Output 85
Analog Output, Manual Control, Inverted Output 86
ON/OFF Output, Automatic Control, Inverted Output C0
ON/OFF Output, Manual Control, Inverted Output C4