2-2

2.2 Control Capability

Number of Loops:

12, Dual Output.

Control Outputs:

Cycle Time Proportioning, Distributed Zero Crossing, or On/Off;

all independently selectable for each loop.

Control Action:

Reverse [heat] or Direct [cool], independently selectable for each

loop.

Digital Control Outputs:

Nominal 5vdc at 10ma to driveoptically- isolated solid-state relays.

Cycle Time:

Programmable foreach loop, 1-255 secs.

Output Resolution:

16 bits.

2.3 Digital Outputs

Number:

11

Configuration:

1 Global Alarm

9 for alarms or events.

1 not used standard PROM

2.4 Digital Inputs

Number:

9

Configuration:

8 for triggers

1 not used standard PROM

2.5 Serial Interface

Type:

RS-232 or RS-485 4 wire, factory select

Isolation:

RS-232: None.

RS-485: To RS-485 Specification.

Baud Rate:

2400 or 9600, menu selectable.

Protocol:

Form of ANSI X3.28-1976, Compatible with Allen-Bradley PLC,

Half Duplex.

Error Check:

BCC or CRC, menu selectable.

Number of Controllers:

Each communications line: 32 with RS- 485, 1 with RS-232.

2.6 Power Supply