beautypg.com

0 specifications, 1 analog inputs, 0 specifications -1 – Watlow 12LS Controller User Manual

Page 12: 1 analog inputs -1

background image

2-1

2.0 SPECIFICATIONS

2.1 Analog Inputs

Analog Inputs

12, Solid state, common ground.

Isolation:

Between inputs and ground: 10volts peak.

A/D Converter:

Integrating voltage to frequency.

Range:

-10 to 60mv, can be changed with scaling resistors to any range

from 0 up to 25v.

Resolution:

0.02%, greater than 12 bits.

Accuracy:

0.1% at 25°C

Calibration:

Automatic zero and full scale.

Temperature Coef:

Less than 100ppm/°C, 0.01%/°C.

Normal Mode Rejection:

60db at 60Hz, full scale range maximum.

Loop Update Time:

1 time per second, every input.

Thermocouple Inputs:

J, K, T, B, S, and R. Measurement Ranges:

J -350 to 1500 B 150 to 3200
K -450 to 2700 S 0 to 3200
T -300 to 800 R 0 to 3210

T/C Break:

Pulse type for up scale break.

Milliamp Inputs:

4-20ma, 10-50ma, 0-50ma, etc. with scaling resistors.

Infrared Inputs:

Power supply included, withscaling resistors.

Source Impedance:

Measurements are within specification with up to 500 ohms source

resistance.