5 setup alarms, 5 setup alarms -28 – Watlow 12LS Controller User Manual
Page 61

4-28
Press UP and DOWN to set the maximum output power percentage from 0 t 100%.
Press ENTER to store the output limit or BACK to return to the SETUP LOOP OUTPUTS main menu prompt.
Entering 100% as the limit effectively disables the limit function.
4.5.4.5 OUTPUT LIMIT TIME
The length of time that a programmed output limit (ref. sec. 4.5.4.4) will be in effect is selectable from 1 to 999
seconds (1 second to over 16 minutes) or CONTINUOUS. The lower line of the display will appear as:
|----------------|
¦ ¦
¦LIMIT TIME ? xxx¦
|----------------|
Press YES to select the menu or NO to advance to the next menu.
Press UP and DOWN to adjust the limit time in seconds.
Press ENTER to store the output limit time and return to the SETUP LOOP OUTPUTS main menu prompt or press
BACK to return to the main menu prompt without storing the data.
4.5.5 SETUP ALARMS
This main menu heading provides access to sub-menus allowing programming of parameters related to the alarm
functions for the selected loop. Press YES at this prompt to edit :
o High process alarm
- High process alarm ON/OFF
- High process alarm output assignment
o Deviation band alarm
- Deviation alarm ON/OFF
- High deviation alarm output assignment
- Low deviation alarm output assignment
o Low process alarm
- Low process alarm ON/OFF
- Low process alarm output assignment
o Alarm Deadband
|-----------------------------------------------------|
¦ NOTE: For all output assignments to alarm functions ¦
¦it must be remembered that all digital outputs are ¦
¦"OR"'d together. More than one alarm function may ¦
¦ be assigned the same output number and that output ¦
¦ will be on if any alarm activates it. ¦
|-----------------------------------------------------|