An example display follows:
|----------------|
¦05 A SEG01/07 R ¦
¦TIME LEFT= 34:28¦
|----------------|
In this example loop 5 is running profile A. The loop is currently executing segment 1 of a total of
7 segments in the profile. The total time remaining in the profile is 34:28. This could be either 34
hours and 28 minutes or 34 minutes and 28 seconds.
4.6.6 CYCLE COUNT DISPLAY
This display shows the profile status on the top line and the current cycle count on the bottom line.
The cycle count is incremented automatically each time the profile is repeated. If (C)ontinuous
cycling is selected only the current cycle number is displayed. If a specific number of cycles has
been specified the current cycle number and the total number to complete will be displayed.
An example of the display when limited cycling has been selected is:
|----------------|
¦05 A SEG01/07 R ¦
¦CYCLE NR= 6/12¦
|----------------|
In this example loop 5 is executing profile A for the 6th time. The profile will be repeated 12
times.
An example of the display for (C)ontinuous cycling is :
|----------------|
¦05 A SEG01/07 R ¦
¦CYCLE NR= 123 ¦
|----------------|
In this example loop 5 is executing profile A for the 123rd time.
4.6.7 PROFILE OPERATION MENU
This menu displays the profile status on the top line and allows for selecting certain modes of
operation related to executing the ramp and soak profile on the bottom line.
The mode selections available depend on the current status of the loop. The following table