PS-3650A / PS-3651A User Manual
3-4
• Be sure that the ambient operation temperature and the ambient humidity are within
their designated ranges. When installing the PS-A on the panel of a cabinet or
enclosure, “Ambient operation temperature” indicates both the panel face and
cabinet or enclosure’s internal temperature.
• Be sure that heat from surrounding equipment does not cause the PS-A to exceed
its standard operating temperature.
• When installing the PS-A in a slanted panel, the panel face should not incline more
than 30°.
• When installing the PS-A in a slanted panel, and the panel face inclines more than
30°, the ambient temperature must not exceed 40°C. You may need to use forced
air cooling (fan, A/C) to ensure the ambient operating temperature is 40°C or below.
• The PS-A Series unit does not support longitudinal mounting.
50 [1.97]
30[1.18]
30[1.18]
Panel
face
Inside of the
enclosure
Unit: mm [in.]
30° or less