beautypg.com

Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 43

background image

43

*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 Total input system transfer time

= sample repetition × 2 + internal operation time +1 scan time.

The value is the maximum time.

For Thermocouple,

as for revision “PV: 03 RL: 07 SV: 1.2”, Typ 33ms + 1 scan time

as for revision “PV: 04 RL: 08 SV: 2.0”, Typ 36.5ms + 1 scan time

For Temperature Probes,

as for revision “PV: 03 RL: 07 SV: 1.2”, Typ 43ms + 1 scan time

as for revision “PV: 04 RL: 08 SV: 2.0”, Typ 26.5ms + 1 scan time

*4 The input value per 1 bit is as shown in the table. LT truncates a number to the 2nd decimal places.

EX.) LT shows 100.1

°C

for the value, 100.15

°C

.

*5 If the input data is not in the range, the error code RGEF130 (Input data error) is output for the analog

module. Once the error occurs, input data from the point of the error is no longer updated. For more

information about error codes, read the “Maintenance/Troubleshooting Guide”.

*6 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it

is in the specified input range. Before inputting the value, therefore, consider the maximum error.

Data

Data Type in
Application
Program

Per 0.1degrees°C (Type K: 0.0 to 1300.0 degrees°C)
Per 0.1 degree°F (Type K: 32.0 to 2372.0 degrees°F)

Monotonicity

Yes

Input Data Out of
Range

Detectable

*5*6

Noise
Resistance

Maximum
Temporary
Deviation during
Electrical Noise
Tests

±3% maximum

*1

or ±1%

maximum

*2

when a 1 kV

clamp voltage is applied to
the I/O wiring and 1 kV is
applied to the power directly.

Accuracy is not assured
when noise is applied.

Common Mode
Characteristics

Common mode reject ratio (CMRR): -50 dB

Common Mode
Voltage

16 VDC

Input Filter

No

Crosstalk

2 LSB max.

Voltage Endurance

500 V between input and power circuit

Isolation Method

Photocoupler Isolation between input and internal
circuit

Selection of Analog Input
Signal Type

Using software programming

Calibration or Verification to
Maintain Rated Accuracy

Approximately 10 years

Disconnection detection

No

External Connection

11-pin terminal connector

Model No.

EXM-ALM3LT

Analog Output Specifications

Voltage Output

Current Output

Rated Output Voltage Range

From DC0 to 10 V

From DC4 to 20 mA

EXM-ALM3LT

Characteristics of Thermocouple
& Temperature Inputs

Thermocouple

Temperature Probes