10 2-ch analog-output module – Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 33
33
Wiring
indicates a fuse.
• The power for the analog module should be supplied separately from the LT.
Turn the analog module on before turning the LT on. Wait at least 30 seconds
after power-off to restart the external power-supply or it may not operate properly.
• Be sure the analog OUT lines are placed in a separate duct from high-frequency,
live lines such as high-voltage, high-power lines, inverters, etc.
• Connect a fuse appropriate for the applied voltage and current draw, at the position shown
in the diagram.
• Do not connect any wiring to unused channels.
15.10 2-ch analog-output module
The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated input
voltage ranges from DC19.2 to 30 V including ripple. The consumption current is 60 mA
(24 VDC) when the input is not-open, output 100%.
EXM-AVO2HT
Analog Output Specifications
Voltage Output
Rated Output Voltage Range
From DC -10 to +10 V
Load
Load Impedance
3 k
Ω min.
Application Load Type
Resistive load
D-A
Conversion
Conversion Time
2 ms
Total Output System
Transfer Time*
1
2 ms + 1 scan time
- +
+
-
+
-
OUT
+
-
Analog voltage/
current input
device
24 VDC
24
VDC
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"