Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 25
25
*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 Total input system transfer time = sample repetition
× 2 + internal operation time + 1 scan time.
As for revision “PV: 03 RL: 07 SV: 1.2”, the value is maximum time. Typ. 33ms + 1 scan time.
As for revision “PV: 04 RL: 08 SV: 2.0”, the value is maximum time. Typ. 26.5ms + 1 scan time.
*4 The 12-bit data (0 to 4095) and 10-bit data (0 to 1023) processed in the Analog I/O module can be linear
converted to a value between -32768 and 32767.
The Optional range designation and analog I/O data minimum and maximum values can be selected using
data registers allocated to analog I/O modules.
*5 As for voltage input data out of range (less than DC 0V, more than DC 10V), or current input data out of
range (less than DC 4mA, more than DC 20mA), the error code RGEF130 (Input data error) is output for
the analog module. Once the error occurs, input data from the point of the error is no longer updated. For
more information about error codes, read the “Maintenance/Troubleshooting Guide”.
*6 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it
is in the specified input range. Before inputting the value, therefore, consider the maximum error.
Wiring
indicates a fuse.
• The power for the analog module
should be supplied separately from
the LT.
Turn the analog module on before
turning the LT on. Wait at least 30
seconds after power-off to restart the
external power-supply or it may not
operate properly.
• Be sure the analog OUT lines are
placed in a separate duct from high-
frequency, live lines such as high-volt-
age, high-power lines, inverters, etc.
Maximum Permanent Allowed Overload
(No Damage)
13 VDC
40 mA DC
Selection of Analog Input Signal Type
Using software programming
Calibration or Verification to Maintain
Rated Accuracy
Approximately 10 years
Disconnection detection
No
External Connection
11-pin terminal connector
EXM-AMI2HT
Characteristics of Analog Voltage Inputs Voltage Input
Current Input
- +
+
-
+
-
+
-
IN0
IN1
+
-
NC
+
-
Analog voltage/
current output
device
Analog voltage/
current output
device
24 VDC
24
VDC
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"