Input Circuit Drawings
Internal Circuit
Wiring
indicates a fuse.
indicates load.
• Since the output terminals are not electrically protected, an output line might be shortcir-
cuited or a connection fault might damage this product. Please install an applicable fuse to
prevent an overload in the circuit, if necessary.
Maximum Load
Voltage
Per Channel
0.3 A
0.1 A
Per Common 3 A
1 A
Output Protection Type
Output is unprotected
Output Voltage Drop
1 VDC or less (voltage between COM and output
terminals when output is on)
Clamp Voltage
39 VDC ±1 V
Voltage Leakage (when OFF)
0.1 mA or less
Output Delay
Time
OFF-ON
300 µs or less
ON-OFF
300 µs or less
Isolation Method
Between output terminals and internal circuit:
photocoupler isolated
Between output terminals: not isolated
External Connection
10-pin terminal
connector
MIL connector
EXM-DDO8TT
EXM-DDO16TK
Internal
Circuit
Output
L
Q0
0
Q1
1
Q2
2
Q3
3
Q4
4
Q5
5
Q6
6
Q7
7
COM(+)
-V
20 Q0
•
Q1
•
Q2
•
Q3
•
Q4
•
Q5
•
Q6
•
Q7
•
COM(+)
2
-V
Q8
19
Q9
•
Q10
•
Q11
•
Q12
•
Q13
•
Q14
•
Q15
•
COM(+)
•
-V
1
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"