*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 Total input system transfer time = sample repetition

× 2 + internal operation time +1 scan time.

As for revision "PV: 03 RL: 07 SV: 1.2", the value is maximum time. Typ. 33ms + 1 scan time.
As for revision "PV: 04 RL: 08 SV: 2.0", the value is maximum time. Typ. 26.5ms + 1 scan time.

*4 The 12-bit data (0 to 4095) and 10-bit data (0 to 1023) processed in the Analog I/O module can be linear

converted to a value between -32768 and 32767.
The Optional range designation and analog I/O data minimum and maximum values can be selected using
data registers allocated to analog I/O modules.

*5 As for voltage input data out of range (less than DC 0V, more than DC 10V), or current input data out of

range (less than DC 4mA, more than DC 20mA), the error code RGEF130 (Input data error) is output for
the analog module. Once the error occurs, input data from the point of the error is no longer updated. For
more information about error codes, read the “Maintenance/Troubleshooting Guide”.

*6 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it

Input Error Maximum Error at 25°C (77°F) ±0.2% of full scale

Temperature Coefficient

±0.006% of full scale/°C

Repeatable After
Stabilization Time

±0.5% of full scale

Nonlinear

±0.2% of full scale

Maximum Error

±1% of full scale

Data

Digital Resolution

4096 increments (12 bits)

Input Value of LSB

2.5 mV

4 µA

Data Type in Application
Program

0 to 4095 (12 bit data)
-32768 to 32767 (optional range designation)*

4

Monotonicity

Yes

Input Data Out of Range

Detectable*

5

*

6

Noise
Resistance

Maximum Temporary
Deviation during Electrical
Noise Tests

±3% maximum when a 1 kV clamp voltage
is applied to the I/O wiring and 1 kV is
applied to the power directly.

Common Mode Characteristics Common mode reject ratio (CMRR): -50 dB
Common Mode Voltage

16 VDC

Input Filter

No

Cable

Twisted-pair shielded cable is
recommended for improved noise immunity

Crosstalk

2 LSB max.

Voltage Endurance

500 V between input and power circuit

Isolation Method

Photocoupler between input and internal circuit

Maximum Permanent Allowed Overload
(No Damage)

13 VDC

40 mA DC

Selection of Analog Input Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

Disconnection detection

No

External Connection

11-pin terminal connector

EXM-AMM3HT

Characteristics of Analog Voltage Inputs

Voltage Input

Current Input