beautypg.com

12 4-ch analog-input/2-ch analog-output module, 12 4-ch analog-input/2-ch analog, Output module – Proface AGP3500 - 10.4 DIO HMI" User Manual

Page 39

background image

39

15.12 4-ch analog-input/2-ch analog-output module

The detail of the external power supply is: the rated supply voltage is 24 VDC, the rated
input voltage ranges from DC20.4 to 28.8 V. The consumption current is 80 mA (24 VDC)
when the input is not-open, output 100%. You can select voltage or current for each input or
output channel.

EXM-AMM6HT

Characteristics of Analog Voltage Inputs

Voltage Input

Current Input

Input Range

DC0 to 10 V

DC4 to 20 mA

Input Impedance

1 M

250

 max.

Input Points

4 points

A-D
Conversion

Sample Repetition Time

64 ms

Total Input System
Transfer Time*

1

4x64 ms + 1 scan time

Input Type

Non differential input

Operating Mode

Self-scan

Conversion Mode

 type ADC

Input Error

Maximum Error at 25°C
(77°F)

±0.5% of full scale

Temperature Coefficient

±0.015% of full scale/°C

Characteristics
of Voltage &
Current Inputs

Repeatable after
Stabilization Time

±0.5% of full scale

Nonlinear

±0.4% of full scale

Maximum Error

±1% of full scale

Data

Digital Resolution

4096 increments (12 bits)

Input Value of LSB

2.5 mV

4.8 µA

Data Type in Application
Program

0 to 4095 (12 bit)
Custom range up to -32768 to +32767*

2

Input Data Out of Range

Detectable*

3

*

4

Noise
Resistance

Maximum Temporary
Deviation during Electrical
Noise Tests

±2% of full scale

Cable

Twisted-pair shielded cable is
recommended for improved noise
immunity

Crosstalk

1 LSB max.

Voltage Endurance

800 VAC

Isolation Method

Photocoupler Isolation between inputs,
and internal circuits

Maximum Permanent Allowed Overload
(No Damage)

30 VDC

40 mA

Selection of Analog Input Signal Type

Using software programming

Calibration or Verification to Maintain
Rated Accuracy

Approximately 10 years

External Connection

10-pin terminal connector