15.4 8-point/16-point relay-output module

RELAY OUTPUTS WELDED CLOSED

• Always protect relay outputs from inductive alternating current load damage using an

appropriate external protective circuit or device.

• Do not connect relay outputs to capacitive loads.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

EXM-DRA8RT

EXM-DRA16RT

No. of Output Points

8 points
(4 points/1 common)

16 points
(8 points/1 common)

*1

*1 When connecting to Hybrid Terminal Block (HTB), up to 6 EXM-DRA16RT (up to 96 points

of the total output points of EXM-DRA16RT) can be connected. When connecting EXM-
DRA16RT up to 6, the following output modules cannot be connected to as the 7th module;
EXM-DRA8RT,EXM-DRA16RT, EXM-DDO8UT, EXM-DDO8TT, EXM-DDO16UK, EXM-
DDO16TK, EXM-DMM8DRT.

No. of Common

2

Output Method

1a-contact

Maximum
Load Voltage

Per Channel

2 A or less

Per Common

7 A or less

8 A or less

Maximum Load Voltage

0.1 mA/0.1 VDC (reference value)

Contact Rating

240 VAC, 2 A (resistance load, cos

θ=0.4 induced

load)
30 VDC, 2 A (resistance load, L/R-7 ms induced load)

Initial Shorting Resistance

30 m

Ω max.

Electrical Life

100,000 operations or more
(rated resistive load 1,800 operations/h)

Mechanical Life

20 million operations or more
(no load 18,000 operations/h)

Voltage Endurance

Between output to terminals: 1500 VAC, 1 minute
Between output terminal and internal circuit: 1500 VAC,
1 minute
Between output groups: 1500 VAC, 1 minute

Output Delay Time

External Connection

11-pin terminal connector 10-pin terminal connector

Command

Output
Relay
Status

OFF delay: 10 ms max.
Contact bounce: 6 ms max.
ON delay: 6 ms max.

ON
OFF

ON
OFF