Proface AGP3500 - 10.4 DIO HMI" User Manual
Page 37
37
is in the specified input range. Before inputting the value, therefore, consider the maximum error.
*1 Compatible with models that have revision “PV: 03 RL: 07 SV: 1.2”. Please refer to “Revision” on page 5.
*2 Compatible with models that have revision “PV: 04 RL: 08 SV: 2.0”. Please refer to “Revision” on page 5.
*3 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value
between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.
EXM-AMM3HT
Analog Output Specifications
Voltage Output
Current Output
Rated Output Voltage Range
From DC0 to 10 V
From DC4 to 20 mA
Load
Load Impedance
2 k
Ω min.
*1
, 1 k
Ω min.
*2
300
Ω max.
Application Load Type
Resistive load
D-A
Conversion
Conversion Time
50 ms
*1
10 ms
*2
Total Output System
Transfer Time
50 ms + 1 scan time
*1
10 ms + 1 scan time
*2
Output
Error
Maximum Error at 25°C (77°F) ±0.2% of full scale
Temperature Coefficient
±0.015% of full scale/°C
Repeatable after
Stabilization Time
±0.5% of full scale
Output Voltage Drop
±1% of full scale
-
Nonlinear
±0.2% of full scale
Output Ripple
1 LSB max.
Overshoot
0%
Total Error
±1% of full scale
Data
Digital Resolution
4,096 increments (12 bits)
Output Value of LSB
2.5 mV
4 µA
Data Type in Application
Program
0 to 4095 (12 bit data)
-32768 to 32767 (optional range designation)
*3
Monotonicity
Yes
Current Loop Open
-
Not detectable
Noise
Resistance
Maximum Temporary
Deviation during Electrical
Noise Tests
±3% maximum
*1
or ±1% maximum
*2
when a
1 kV clamp voltage is applied to the I/O wiring
and 1 kV is applied to the power directly.
Cable
Twisted-pair shielded cable is
recommended for improved noise immunity
Crosstalk
No crosstalk because of 1 channel output
Voltage Endurance
500 V between output and power circuit
Isolation Method
Photocoupler Isolation between output and
internal circuit
Selection of Analog Output Signal Type
Using software programming
Calibration or Verification to Maintain
Rated Accuracy
Approximately 10 years
Disconnection detection
No
External Connection
11-pin terminal Connector
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"