*1 Total input system transfer time = sample repetition × 2 + 1 scan time.
*2 The 12-bit data (0 to 4095) processed in the Analog I/O module can be linear converted to a value
between -32768 and 32767. The optional range designation and analog I/O data minimum and maximum
values can be selected using data registers allocated to analog I/O modules.
*3 If the input data is not in the range, the error code RGEF130 (Input data error) is output for the analog
module. Once the error occurs, input data from the point of the error is no longer updated. For more
information about error codes, read the “Maintenance/Troubleshooting Guide”.
*4 The input value may be regarded as "Input Data Out of Range" due to the maximum error even when it
is in the specified input range. Before inputting the value, therefore, consider the maximum error.
*5 Only when connected to Hybrid Terminal Block (HTB)
Data
Digital
Resolution
4096 increments (12 bits)
Input Value of
LSB
2.5 mV
4.8 µA
Pt: 0.20 °C
(32.36 °F)
Ni: 0.05 °C
(32.09 °F)
Data Type in
Application
Program
0 to 4095 (12 bit)
Custom range up to -32768 to
+32767*
2
Celsius /
Fahrenheit
Input Data Out
of Range
Detectable*
3
*
4
Noise
Resistance
Cable
Twisted-pair shielded cable is recommended for
improved noise immunity
Crosstalk
1 LSB max.
Voltage Endurance
2500 VAC between inputs, external power supply
and internal logic circuits
Isolation Method
Photocoupler Isolation between input and internal
circuit (1500 VDC isolation)
Maximum Permanent Allowed
Overload (No Damage)
13 VDC
40 mA
-
Selection of Analog Input Signal
Type
Using software programming
All inputs have the same voltage/current configuration or
temperature. For temperature, it is possible to configure
each channel independently of the type of probe.
Calibration or Verification to
Maintain Rated Accuracy
Approximately 10 years
Default input value in case of
temperature sensor
disconnection
Upper limit
*5
External Connection
11-pin terminal connector
EXM-AMI4LT
Characteristics of Analog Voltage Inputs
Voltage Input
Current Input
Temperature Probes
- AGP3400 - 7.5 DIO HMI" AGP3300 - 5.7 DIO HMI" AGP3600 - 12.1 FLEX Network HMIs" AGP3500 - 10.4 FLEX Network HMI" AGP3400 - 7.5 FLEX Network HMI" AGP3600 - 12.1 CANopen HMI" AGP3500 - 10.4 CANopen HMI" AGP3400 - 7.5 CANOpen HMI" AGP3300 - 5.7 CANopen HMI" LT3200 - 3.8 All-in-One HMI" AGP3300H - 5.7 Handheld HMIs" AGP3750 - 15 Multi-Media HMI" AGP3650 - 12.1 Multi-Media HMIs" AGP3550 - 10.4 Multi-Media HMIs" AGP3450 - 7.5 Multi-Media HMI" AGP3360 - 5.7 Multi-Media HMI" AST3300 - 5.7 Basic HMI" AST3200 - 3.8 Basic HMI" AGP3600 - 12.1 Standard HMIs" AGP3500 - 10.4 Standard HMIs" AGP3400 - 7.5 Standard HMI" AGP3300 - 5.7 Standard HMI" AGP3200 - 3.8 Standard HMI"