beautypg.com

Maple Systems OIT Family (ASCII) User Manual

Page 38

background image

ASCII String: This format is used to represent a single coil in the OIT as a binary value with

user-definable strings that will indicate whether the coil is on or off. The strings can be up to

eight characters in length. Two ASCII strings are created to represent the OIT coil when it is

on or off. For example, the ASCII string Running may be created to represent the OIT coil

when it is on and the ASCII string Stopped may be created to represent the OIT coil when it

is off. A maximum of 30 ASCII strings may be programmed into the OIT, with each OIT coil

capable of using any two of the ASCII strings. All of the ASCII strings can be shorter than

eight characters in length. Therefore, the length of the monitor should be set to match which-

ever of the two ASCII strings referenced is longer.

Bar Graph (OIT5400 only): This format is used to represent a signed 16-bit register as a bar

graph. The bar graph can be setup as a horizontal or vertical bar graph. The width and height

of the bar graph can be defined, as well as adding a percentage sign that is displaced in the

middle of the bar graph. Low and high limits are established to set the range that the bar

graph will cover. (Example: If the register range always falls within -100 to +100, then the

low and high limits for the bar graph are set accordingly for maximum resolution.)

Register Monitor Attributes

Adjustable Register Monitor Width: When register monitors are embedded into a screen

within the OIT, the number of character positions that the monitor occupies is programmable. This

isusefulforshorteningthenumberofcharacterpositionsaregistermonitorrequireswhentherange

of data is known. For example, there is no reason to display five characters for the Decimal format

when the system programmer knows that the register monitor being displayed never exceeds 99. In

this case, the system programmer may opt to set the register monitor width to two to save space on

the display. If the data read from the OIT register requires more space than has been allocated to the

register monitor, the overload character ‘#’ will be displayed in each character position within the

register monitor’s data field until a number that is within range is read.

Note: Some of the register monitor field attributes (such as decimal point, commas, etc.) will

increase the number of character positions that the register monitor will occupy on the

screen. When commas are selected, the increase in character positions will be dependent

on the data format and existing field width.

FEATURES

37

1010-0088, REV02

2

3

4

6

5

7

8

MESSAGE ALARM

RUN

PRINT

1

Sw1 Toggles->

Value: Closed

Arm: Up

Actuator: Right

Conveyor: Fast

S1
S2
S3
S4
S5
S6
S7
S8

Message

Alarm

Run

Print