Section 6: Fieldbus/Bluetooth

01/13

40

51297 Rev. 1

5.2.2.

DEVICENET (

29578

), CONTINUED

NETWORK STATUS LED

MODULE STATUS LED

STATE

INDICATION

OFF

Not online/ No power

GREEN

Online, one or more connection established

FLASHING GREEN (1 Hz)

Online, no corrections established

Red

Critical link failure

Flashing Red (1 Hz)

One or more connections timed out

Alternating Red/Green

Self-test

STATE

INDICATION

OFF

No power

GREEN

Operating in normal condition

FLASHING GREEN (1 Hz)

Missing/Incomplete configuration/ Device needs commissioning

Red

Unrecovrerable fault(s)

Flashing Red (1 Hz)

Recoverale fault(s)

Alternating Red/Green

Self-test

1 NS =

Operation Mode

LED

2 MS =

Mode Status

LED

3 Connection = DeviceNet Connector