Pneumatic data, Type label – Burkert Type 8696 User Manual
Page 22
22
Technicaldata
6.5.
Pneumatic data
Control medium
neutral gases, air
Quality classes in accordance with DIN ISO 8573-1
Dust content
Class 5
max. particle size 40 µm,
max. particle density 10 mg/m³
Water content
Class 3
max. pressure dew point
- 20 °C or min. 10 °C below the lowest operating temperature
Oil content
Class 5
max. 25 mg/m³
Temperature range
of the compressed air
0 – + 50 °C
Pressure range
3 – 7 bar
Air output, pilot valve
7 I
N
/min (for aeration and deaeration)
(Q
Nn
value according to definition for pressure drop from 7 to 6 bar absolute)
Connections
23xx / 2103 (Element)
Plug-in hose connector Ø 6 mm / 1/4”
Threaded port G1/8
Model third-party device:
Socket connection G 1/8
with M5 connection for connecting to the third-party device
6.6.
Type label
Example:
8696 24 V DC
single act Pilot 0.6
Pmax 7 bar
Tamb 0°C - +55°C
S/N 001000
00177689
D-74653 Ingelfingen
W14UN
CE
Identification number
Supply voltage / Control
Max. pressure
Type
Control function - Pilot valve
Bar code
Serial number - CE mark
Max. ambient temperature
Figure 8:
Example of type label
english
Type 8696