Part 3 - keypad configuration – Dynasonics TFXM Series Ultrasonic Multi-Channel Flow Meter User Manual

Page 66

  • Text mode
  • Original mode
background image


Rev. 8/02

-3. 28-

TFXM

??

An out-of-round pipe, carrying water, causes the TFXM to
indicate a measured sound speed that is 7.4% lower than
the TABLE 3.1 value. This pipe condition will cause the
flow meter to indicate flow rates that are 7.4% lower than
actual flow. To correct the flow readings, enter 1.074.








PART 3 - KEYPAD CONFIGURATION

Pages: 1 … 64 65 66 67 68 … 107
  • wrong Brand
  • wrong Model
  • non readable
See also other documents in the category Dynasonics Equipment:
  • TFXL Clamp-On Ultrasonic Flow (44 pages)
  • TFX Ultra Transit Time Flow Meters (108 pages)
  • UFX ULTRASONIC FLOW METER (16 pages)
  • 902_903 Series Portable Doppler Ultrasonic Flow Meter (48 pages)
  • DDFXD Doppler Ultrasonic Flow Meter (65 pages)
  • DXN Portable Ultrasonic Measurement System (108 pages)
  • DXN Portable Ultrasonic Measurement System Firmware Update (16 pages)
  • Fusion Water Flow Meter (48 pages)
  • MFX Series Insertion MagProbe Flow Meter (88 pages)
  • PFP-600 (17 pages)
  • D7700 Series Insertion Doppler Ultrasonic Flow Meter (42 pages)
  • 701_771C Series Insertion Ultrasonic Flow Meter (50 pages)
  • 901 Series Enhanced Ultrasonic Flow Meter (45 pages)
  • D601 Series Doppler Ultrasonic Flow Meter (48 pages)
  • D300_301 Series Doppler Ultrasonic Flow Meter (38 pages)
  • TFXP Series Transit Time Ultrasonic Flow Meter (132 pages)
  • WT-1 ULTRASONIC THICKNESS GAUGE (2 pages)
Home Brands Popular manuals Recently added
Manuals Directory

© 2012–2025, azmanual.top
All rights reserved.