Alpha Technologies Cordex Controller Ver.3.1x User Manual
Page 87
85
0700015-J0 Rev B
6.7.3.5 Example Two – Battery System
The following is an example of a Data Log configured to monitor the battery voltage, current, temperature
and other parameters for a battery system.
1. From the web interface, select
Signals > Configure Data Logging
.
2. Under
Data Log Files
, select an unused log file to edit.
3. Enter a filename description under
File Information
.
4. Enter the number of
Log Records
you want to keep and select
FIFO
as the
File Save Option
.
5. Under
Start Trigger
and
Stop Trigger
, select
Manual
for each.
6. Under
Log Frequency
, select
Enable Signal Interval
.
7. Click the
Log Signals
button to select the battery signals for logging.
8. Select
Controller Signals
from the Signal List in the Configure Signals window.
9. Scroll down and check each battery signal as shown.
10. Select
Apply
(to accept changes and return to Configure Data Logging window).
11. Click the
Save
icon to save the changes and click
Accept
when prompted.
12. Start the log by clicking the
Start
button located next to the File Information heading (see Figure 90).
Once the data has collected for the desired interval, return to this window and click the
Stop
button.
13. Select
Logs & Files > Retrieve Logs
. Select the file name from the pull-down menu and then select
Data Log
to view the log information in a new window. Copy and paste the data into a spreadsheet
application for analysis.
Figure 97 — Configure (Signals) Data Logging web interface window, example two
Figure 98 — Enable (Controller) Signals for Data Logging web interface