Table U — CXC Modbus PDU address definition for function code 0x03 (read holding registers)
PDU Address
Variable Name
Variable Description
Number of
Bytes
0x018A
Signal_5_In_Signal_Table_5
Timer 5
4 (signed int_32)
0x018C
Signal_6_In_Signal_Table_5
Timer 6
4 (signed int_32)
0x018E
Signal_7_In_Signal_Table_5
Timer 7
4 (signed int_32)
0x0190
Signal_8_In_Signal_Table_5
Timer 8
4 (signed int_32)
0x0192
Signal_9_In_Signal_Table_5
Timer 9
4 (signed int_32)
0x0194
Signal_10_In_Signal_Table_5
Timer 10
4 (signed int_32)
0x01C2
Signal_1_In_Signal_Table_6
Counter 1
4 (signed int_32)
0x01C4
Signal_2_In_Signal_Table_6
Counter 2
4 (signed int_32)
0x01C6
Signal_3_In_Signal_Table_6
Counter 3
4 (signed int_32)
0x01C8
Signal_4_In_Signal_Table_6
Counter 4
4 (signed int_32)
0x01CA
Signal_5_In_Signal_Table_6
Counter 5
4 (signed int_32)
0x01CC
Signal_6_In_Signal_Table_6
Counter 6
4 (signed int_32)
0x01CE
Signal_7_In_Signal_Table_6
Counter 7
4 (signed int_32)
0x01D0
Signal_8_In_Signal_Table_6
Counter 8
4 (signed int_32)
0x01D2
Signal_9_In_Signal_Table_6
Counter 9
4 (signed int_32)
0x01D4
Signal_10_In_Signal_Table_6
Counter 10
4 (signed int_32)
Table V — CXC Modbus PDU address definition for function code 0x04 (read input registers)
PDU
Address
Variable Name
Variable Description
Response
Data
Format
0x0001
Relays_Total (Y)
Read number of relays
BINARY
0x0002
Total_Active_Alarms (Z)
Read total active alarms
BINARY
0x0003
System_Major_Alarm
Read system major alarm status
BINARY
0x0004
System_Minor_Alarm
Read system minor alarm status
BINARY
0x0011
Alarm_Tables_Total (X)
Read number of alarm tables (X<=0x1E)
BINARY
0x0012
Alarms_Total_In_Alarm_Table _1 (A1)
Read number of alarm in alarm table 1 (A1
<= 0x3F)
BINARY
0x0013
Alarms_Total_In_Alarm_Table _2 (A2)
Read number of alarm in alarm table 2 (A2
<= 0x3F)
BINARY
0x0011 + X Alarms_Total_In_Alarm_Table _X (AX)
Read number of alarm in alarm table X (AX
<= 0x3F)
BINARY
0x0031
Number_of_Active_Alarms_In_Alarm_table _1
Read number of active alarms in alarm
table 1
BINARY
0x0032
Number_of_Active_Alarms_In_Alarm_table _2
Read number of active alarms in alarm
table 2
BINARY
0x0031 +
(X-1)
Number_of_Active_Alarms_In_Alarm_table _X
Read number of active alarms in alarm
table X
BINARY