Table i — alarms menu defaults – Alpha Technologies Cordex Controller Ver.3.1x User Manual
Page 124
0700015-J0 Rev B
122
Table J — Alarms menu defaults
Submenu Item
Programmable
Range
Default Setting: Priority, Activation Value
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
Rectifier Fail
Major/Minor/Message Minor
Rectifier Minor
Major/Minor/Message Minor
Rect. Major Fail Count
Major/Minor/Message Major, 2
Rect. Minor Fail Count
Major/Minor/Message Minor, 1
Rectifier Lockout
Major/Minor/Message Minor
Out of Tolerance
Major/Minor/Message Minor
Rect. Communications Lost
Major/Minor/Message Minor
Rect. Equalize Activated
Major/Minor/Message Minor
Rect. AC Mains Fail
Major/Minor/Message Minor
Max. Rectifiers Exceeded
Major/Minor/Message Minor
Fan Fail Alarm
Major/Minor/Message Minor
Power Save
Major/Minor/Message
Distribution Fuse (Digital 1)
Major/Minor/Message Minor, High
Battery Fuse (Digital 2)
Major/Minor/Message Major, High
LVD Manual In (Digital 3)
Major/Minor/Message Minor, High
LVD Manual Out (Digital 4)
Major/Minor/Message Major, High
Converter Fail (Digital 5)
Major/Minor/Message Minor, High
Conv. I/P Breaker Trip (Digital 6)
Major/Minor/Message Major, High
Digital 7-8
Major/Minor/Message Message, High
Battery Current High
Major/Minor/Message Major, 100A
Load Current High
Major/Minor/Message Major, 1000A
AC Mains High
Major/Minor/Message Minor,
270V
Minor,
270V
Minor,
270V
Minor,
270V
Minor,
270V
AC Mains Low
Major/Minor/Message Minor,
180V
Minor,
180V
Minor,
180V
Minor,
180V
Minor,
180V
High Voltage 1
Major/Minor/Message Minor,
14.00V
Minor,
28.00V
Minor,
55.50V
Minor,
134.13V
Minor,
235.88V
High Voltage 2
Major/Minor/Message Major,
14.25V
Major,
29.00V
Major,
56.50V
Major,
136.54V
Major,
240.13V
Low Voltage 1
Major/Minor/Message Minor,
12.00V
Minor,
24.00V
Minor,
48.00V
Minor,
116.00V
Minor,
204.00V
Low Voltage 2
Major/Minor/Message Major,
11.62V
Major,
23.25V
Major,
46.50V
Major,
112.38V
Major,
197.63V
Midpoint Monitor 1-5
Major/Minor/Message Minor, 0.50V
Battery Runtime Low
Major/Minor/Message Minor, 3 hours
Battery Capacity Low
Major/Minor/Message Minor, 80%
Battery Overtemp
Major/Minor/Message Minor, 40ºC
Battery On Discharge
Major/Minor/Message Major
Temp Sensor 1-5 Fail
Major/Minor/Message Message
TC Sensor Fail
Major/Minor/Message Message
Miscellaneous/Real Time Clock Error
Major/Minor/Message Minor
Custom 1-20
See 6.5.3.10
Message
Relay Mapping System Major
See 6.5.3.8
Major, Relay 5
System Minor
See 6.5.3.8
Minor, Relay 4