6.6.5 Menu Items for Configuring Alarms Associated with Each Analog Input
6.6.5.1 Current Alarms
Battery Current High
Setting for the battery amps alarm. When the total current to the battery
exceeds this setting, the alarm is activated and the message
BATTERY
CURRENT HIGH
is displayed on the GUI.
Load Current High
Setting for the load amps alarm. When the current to the load has exceeded
this setting, an alarm is activated and the message
LOAD CURRENT HIGH
is
displayed on the GUI
6.6.5.2 Voltage Alarms
AC Mains High
Activates an alarm when the AC exceeds the specified setting. The message
AC MAINS HIGH
displays on the GUI.
AC Mains Low
Activates an alarm when the AC input to the power system falls below the
specified setting. The message
AC MAINS LOW
displays on the GUI.
High Voltage [1-2]
Activates an alarm when the power system DC voltage exceeds the specified
value. The message
HIGH VOLTAGE 1 (or 2)
displays on the GUI.
Low Voltage [1-2]
Activates an alarm when the power system DC voltage falls below the
specified value. The message
LOW VOLTAGE 1 (or 2)
displays on the GUI.
Midpoint Monitor [1-5]
Activates an alarm when the voltage reading (1 through 5) exceeds the
specified setting (from the midpoint). The message
MIDPOINT MONITOR 1
(or
2-5) displays on the GUI.
6.6.5.3 Battery Alarms
Battery Runtime Low
Allows specification in hours when the battery runtime alarm will activate with
respect to the hours remaining in the battery runtime prediction.
Battery Capacity
(Remaining) Low
Allows specification of the battery capacity alarm trigger point as a
percentage. When the capacity of the battery is depleted to this specified
value, the capacity alarm is activated.
Battery Overtemp
Activates an alarm when the specified temperature is reached.
Battery On Discharge
Activates an alarm when the battery is on discharge; e.g., during AC Fail or
BT mode.
Battery Test
Activates an alarm when the Battery Test is in progress.
Boost Mode
Activates an alarm when BST mode is activated.
6.6.5.4 Temperature Alarms
Temp Sensor Fail [1-4]
Activates an alarm when any temperature sensor fails
TC Sensor Fail
Activates an alarm when a sensor, enabled for Temp Comp, fails