11. Factory Ranges and Defaults
Table G — Rectifiers menu defaults
Submenu Item
Programmable
Range
Default Setting
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
Float (FL) Voltage
0-9999999999
13.50V
27.00V
54.00V
130.50V
229.5V
Equalize (EQ) Voltage
0-9999999999
13.75V
27.50V
55.00V
132.92V
233.75V
Battery Test (BT) Voltage
0-9999999999
11.50V
22.00V
44.00V
106.33V
187.00V
OVP
0-9999999999
14.25V
29.00V
57.00V
137.75V
242.25V
LVA
0-9999999999
11.00V
22.00V
44.00V
106.33V
187.00V
HVA
0-9999999999
14.00V
28.00V
55.50V
134.13V
235.88V
Current Limit (CL)
0-9999999999
100%
Power Limit (PL)
0-9999999999
100%
Equalize Timeout
0-9999999999
30 hours
Battery Test Duration
0-9999999999
8.0 hours
Slope (Adjust)
0-9999999999
1.00%
Backlight Timeout
0-32767
1 minute
Security Code
0-32767
123
Module Start Delay
0-32767
1 second
System Start Delay
0-32767
0 seconds
Soft Start Ramp Rate
Normal/Fast
Normal
Temp Display Scale
Celsius/Fahrenheit
Celsius
Current/Power Limit Alarm
Enable/Disable
Disable
Remote Shutdown
Enable/Disable
Enable
Local Access Alarm
Enable/Disable
Enable
Ramp Test
Enable/Disable
Enable
Power Save
Enable/Disable
Disable
Redundant Rectifiers
0-32767
1
Maximum Power Usage
0-32767
80%
Table H — Converters menu defaults
Submenu Item
Programmable Range
24V–48V Defaults
48V–24V Defaults
Output Voltage
0-9999999999
54.00V
27.00V
OVP
0-9999999999
57.00V
28.50V
Input Voltage Shutdown
0-9999999999
21.0V
42.0V
Input Voltage Restart
0-9999999999
25.0V
50.0V
Start Delay
0-32767
1 second
Current Limit (CL) Alarm
Enable/Disable
Enable