Table R — Inverter Alarm Codes
Alarm Type
Cause
Solution
T2S Event
226
NO TRANSMISSION
Alarm from the T2S - does
not see any TSI- all modules -
system alarm or when the T2S
does not see one of the modules
Replace defective inverter or adapt
configuration
227
DIG INP1 FAILURE
Digital input has changed status
Check device connected on input digital
228
DIG INP2 FAILURE
Digital input has changed status
Check device connected on input digital
229
REDUNDANCY
LOST
Lost of inverter redundancy
Replace defective inverter or adapt
configuration
230
REDUND + 1 LOST
Lost of inverter redundancy + 1
inverter
Replace defective inverter(s) or adapt
configuration
231
SYS SATURATED
Load of system greater than the
preset value
Reduce load or add inverter on the system, or
change the alarm level trigger.
232
MAIN SOURCE
LOST
Priority source lost (depends
on the configuration AC/AC or
Online)
1) In AC/AC configuration: Reconnect AC IN or
check configuration or check live value. 2) In
Online configuration: Reconnect DC or check
configuration or check level voltage
233
SEC SOURCE
LOST
Secondary source lost (depends
on the configuration AC/AC or
Online)
1) In ONLINE configuration: Reconnect AC
IN or check configuration or check live value.
2) In AC/AC configuration: Reconnect DC or
check configuration or check level voltage
234
T2S BUS FAIL
The communication bus to T2S
has failed
Hardware problem. Replace T2S
235
T2S FAILURE
T2S has failed
Hard ware problem. Replace T2S
236
T2S STARTED
T2S has started
237
LOG CLEARED
T2S has cleared the log
238
CONFIG MODIFIED
Configuration is modified
239
NEW MOD
DETECTED
One more module is plugged
240
DATE & TIME MOD
Date and time are modified
241
CFG READ IN MOD
T2S has read the CFG
242
LOG NEARLY FULL
This item will be set as, No
alarm, Minor or major alarm. (see
configuration file)
Clear log file
243
T2S FLASH ERROR
Flash of T2S is corrupt and has
failed
Hardware problem. Replace T2S