Table j — controls menu defaults – Alpha Technologies Cordex Controller Ver.3.1x User Manual
Page 125
123
0700015-J0 Rev B
Table K — Controls menu defaults
Submenu Item
Programmable Range
Default Setting
12Vdc
24Vdc
48Vdc
125Vdc
220Vdc
LVD 1
0-9999999999
10.5V
21.00V
42.00V
101.50V
178.50V
LVC 1
0-9999999999
12.5V
25.00V
50.00V
120.83V
212.50V
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
1
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 2
0-9999999999
10.5V
21.00V
42.00V
101.50V
178.50V
LVC 2
0-9999999999
12.5V
25.00V
50.00V
120.83V
212.50V
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
2
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 3
0-9999999999
10.5V
21.00V
42.00V
101.50V
178.50V
LVC 3
0-9999999999
12.5V
25.00V
50.00V
120.83V
212.50V
Relay Mapping
1-16 or N/A (mapping disabled)
3
Control
Check = enable LVD control
Checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD 4-10
0-9999999999
10.5V
21.00V
42.00V
101.50V
178.50V
LVC 4-10
0-9999999999
12.5V
25.00V
50.00V
120.83V
212.50V
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
LVD Inhibit (Status)
Active/Inactive
Inactive
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
N/A
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
High Volt. Shutdown
0-9999999999
14.25V
29.50V
58.00V
140.17V
246.50V
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked
CEMF In-circuit Voltage
0-9999999999
13.70V
27.40V
54.80V
132.43V
232.90V
Bypass Voltage
0-9999999999
13.55V
27.10V
54.20V
130.98V
230.35V
Alarm Priority
Major/Minor/Message
Major
Relay Mapping
1-16 or N/A (mapping disabled)
N/A
Control
Check = enable LVD control
Not checked
Alarm cutoff
Check = allow alarm to be cutoff
Not checked