Table Q — Inverter Parameters
Submenu Item
Default Setting
Units
AC : Fac_in Low Stop
47.0
Hz
AC : Fac_in High Start
62.7
Hz
AC : Fac_in High Stop
63.0
Hz
AC 1 : Vac_in Low Start
92.5
V
AC 1 : Vac_in Low Transfer
87.5
V
AC 1 : Vac_in Low Stop
87.5
V
AC 1 : Vac_in High Start
133.0
V
AC 1 : Vac_in High Transfer
138.0
V
AC 1 : Vac_in High Stop
138.0
V
AC 2 : Vac_in Low Start
92.5
V
AC 2 : Vac_in Low Transfer
87.5
V
AC 2 : Vac_in Low Stop
87.5
V
AC 2 : Vac_in High Start
133.0
V
AC 2 : Vac_in High Transfer
138.0
V
AC 2 : Vac_in High Stop
138.0
V
AC 3 : Vac_in Low Start
92.5
V
AC 3 : Vac_in Low Transfer
87.5
V
AC 3 : Vac_in Low Stop
87.5
V
AC 3 : Vac_in High Start
133.0
V
AC 3 : Vac_in High Transfer
138.0
V
AC 3 : Vac_in High Stop
138.0
V
AC 4 : Vac_in Low Start
92.5
V
AC 4 : Vac_in Low Transfer
87.5
V
AC 4 : Vac_in Low Stop
87.5
V
AC 4 : Vac_in High Start
133.0
V
AC 4 : Vac_in High Transfer
138.0
V
AC 4 : Vac_in High Stop
138.0
V